Inventário e plano de manutenção, operação e controle aplicado ao Hospital da Criança Santo Antônio

dc.contributor.advisorBartex, Sérgio
dc.contributor.authorBarranco, Anderson Dekert
dc.coverage.spatialPorto Alegrept_BR
dc.date.accessioned2023-09-11T12:56:33Z
dc.date.available2023-09-11T12:56:33Z
dc.date.issued2020-08
dc.description.abstractO objetivo principal deste trabalho é realizar o inventario de máquinas e o projeto do Plano de Manutenção, Operação e Controle (PMOC) do sistema de climatização de ambientes do Hospital da Criança Santo Antônio, localizado dentro do complexo hospitalar da Irmandade Santa Casa de Misericórdia de Porto Alegre para adequar a edificação na Lei nº 13.589, de 4 de janeiro de 2018. Para a realização deste trabalho de pesquisa foram realizadas visitas in loco de todos ambientes do hospital para coleta de informações como: a quantidade de pessoas fixas e flutuantes frequentadoras dos ambientes, identificação do tipo, número de série, número de patrimônio, e potência dos equipamentos de climatização instalados nestes ambientes, consultas em plantas baixas para identificação das áreas e levantamento fotográfico dos tipos de equipamentos, realizando a identificação dos ambientes climatizados juntamente com o inventario dos equipamentos para a melhoria no processo de manutenção preventiva adequando-o conforme a portaria nº 3.523, de 28 de agosto de 1998. Os resultados adquiridos neste estudo, comprovam a necessidade e a possibilidade de implementação do projeto do PMOC em todo o edifício, conforme resultado de análise da qualidade do ar, onde encontrou-se 50% dos locais não adequados aos parâmetros recomendados pela RE nº 9. Sendo 43% dos ambientes com quantidade superiores de Dióxido de Carbono, conforme resolução considera valores menores que 1000 partes por milhão (ppm), e 7% dos ambientes apresentaram contaminação microbiológica na relação I/E fora do parâmetro recomendado, e que 87% dos equipamentos não possuíam manutenção preventiva, sendo os outros 13% equipamentos executados conforme solicitação para vistorias dos órgãos responsáveis.pt
dc.description.abstractThe main objective of this work is to carry out the inventory of machines and the design of the Maintenance, Operation and Control Plan (PMOC) of the air conditioning system of the Hospital da Criança Santo Antônio, located inside the hospital complex of the Irmandade Santa Casa de Misericórdia do Porto Alegre to adapt the building to Law No. 13,589, of January 4, 2018. To carry out this research work, visits were made on site to all hospital environments to collect information such as: a number of frequent fixed and floating people in the environments, type identification, serial number, patrimony number, and power of the air conditioning equipment, environments, consultations in floor plans to identify areas and photographic survey of types of equipment, performing the identification of air conditioned environments used with the inventory of equipment for improvement in the process of adequate preventive maintenance o o as per the ordinance No. 3,523, of August 28, 1998. The results acquired in this study, prove the need and the possibility of implementing the PMOC project in the entire building, as a result of the air quality analysis, where 50% of the places not used by users recommended by RE nº 9 were found. 43% of the environments with a quantity higher than Carbon Dioxide, according to the resolution considers values below 1000 parts per million (ppm), and 7% of the environments contaminated by microbiological contamination in the I / E ratio for recommended parameters, and 87% of the equipment it had no preventive maintenance, the other 13% being equipment executed as requested by the responsible agenciesen
dc.format.extent138 f.pt_BR
dc.identifier.urihttps://repositorio.animaeducacao.com.br/handle/ANIMA/36652
dc.language.isoptpt_BR
dc.rightsAtribuição-NãoComercial-SemDerivados 3.0 Brasil*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/br/*
dc.subjectPMOCpt_BR
dc.subjectQualidade do Arpt_BR
dc.subjectAmbientes Climatizadospt_BR
dc.subjectClimatização em Hospitaispt_BR
dc.titleInventário e plano de manutenção, operação e controle aplicado ao Hospital da Criança Santo Antôniopt_BR
dc.typeMonografiapt_BR
local.author.cursoEngenharia Mecânicapt_BR
local.author.unidadeUNIRITTER / Zona Sulpt_BR
local.dateissued.semester2pt_BR
local.modalidade.estudoPresencialpt_BR
local.rights.policyAcesso abertopt_BR
local.subject.areaEngenhariaspt_BR
local.subject.areaanimaEngenhariaspt_BR

Arquivos

Pacote Original
Agora exibindo 1 - 1 de 1
Nenhuma Miniatura disponível
Nome:
ADB TCC.pdf
Tamanho:
9.34 MB
Formato:
Adobe Portable Document Format
Licença do Pacote
Agora exibindo 1 - 1 de 1
Nenhuma Miniatura disponível
Nome:
license.txt
Tamanho:
923 B
Formato:
Item-specific license agreed upon to submission
Descrição: